Heat Shrinkable Cable Accessories
11Kv Heat Shrinkable Cable Accessories
| Property |
Typical data |
| Ac withstand (under rain) |
45Kv/1min |
| Ac withstand (without rain) |
45Kv/1min |
| Impulse withstand |
±105Kv/10times |
| Dc withstand |
-52Kv/15min |
| Ac withstand |
35Kv/4h |
| Partial discharge test |
≤10PC(1.73Uo) |
11Kv Heat Shrinkable Cable Accessories
24Kv Heat Shrinkable Cable Accessories
| Property |
Typical data |
| Ac withstand (under rain) |
56Kv/1min |
| Ac withstand (without rain) |
56Kv/1min |
| Impulse withstand |
±125Kv/10times |
| Dc withstand |
-96Kv/15min |
| Ac withstand |
48Kv/4h |
| Partical discharge test |
≤10PC(1.73Uo) |
24Kv Heat Shrinkable Cable Accessories
36Kv Heat Shrinkable Cable Accessories
| Property |
Typical data |
| Ac withstand (under rain) |
117Kv/1min |
| Ac withstand (without rain) |
117Kv/1min |
| Impulse withstand |
±250Kv/10times |
| Dc withstand |
-156Kv/15min |
| Ac withstand |
104Kv/4h |
| Partical discharge test |
≤10PC(1.73Uo) |
36Kv Heat Shrinkable Cable Accessories
LV Heat Shrinkable Cable Accessories
| Property |
Typical data |
| Hardness |
80(Shoea A) |
| Tensile strength |
12Mpa |
| Elongation at break |
300% |
| Dielectric strength |
≥20Kv/mm |
| Ac voltage withstand |
2.5Kv |
| Shrink temperature |
120~140℃ |
| Shrink ration (dia) |
250% |
| Longitudinal shrinkage |
±5% |
LV Heat Shrinkable Cable Accessories